Pressurisation equipment for lobbies, compliant with DM 30/11/1983 and designed according to the European standard EN 12101-6
The PRESSKIT equipment is comprised of one or more fans. In the event of a fire, they are activated to exert an overpressure of 50 Pa in safe areas and to prevent the entry of smoke in the evacuation routes for people.
Common features: • Self-regulation of pressure throughout the lobby. • EC brushless fans 24 V DC with a maximum flow of 2100 m3/H. • Maintain an overpressure of 50 Pa in hallways.
CONTROL PANEL • S models: simplified regulation of the ventilation unit by means of a pressure probe with incorporated PID signal regulator. • P models: PLC control with multiple inputs, outputs, alarms and fan regulation through PID signal. • Power panel with autonomy of more than 2 hours using 18Ah batteries. • Easy connection of equipment. • Quick configuration and adjustment of all parameters through LCD screen and keyboard. • MANUAL system activation button. • Real time visualization of the pressure of the safe zone and the status of the equipment. • Control panel of the system by means of a PLC of reduced size and easy installation. 230 VAC power. • Open door detection digital input. • Digital outputs indicating activated fire alarm. By visual and acoustic indicator in intermittent mode with configurable times. • Configurable connection delay times in the event of fire alarm detection and open fire doors. • Visualization of pressure in Pa in real time. Status indication of the STANDBY/PRESSURIZING equipment. • Possibility of controlling 2 fans with a single panel and power supply. (PRESSKIT TWIN). • Key lock.
PRESSURIZATION FAN • Wall fan for 310 mm diameter ducts. • Lifespan in continuous work of more than 20,000 hours. • Impeller made of painted sheet steel. • Anti-contact protection grid.
PRESSURE SENSOR WITH DISPLAY (INCORPORATED IN CONTROL PANEL) • Preset differential pressure sensor of 0-100 Pa. • LCD screen. • High precision calibrated analog sensor.