CJSX 60HZ
400 ºC/2h, belt-driven extractor fan units with single inlet fans
400 ºC/2h extractor fan units. with motor mounted outside the airflow path. for operation outside the fire risk zone
Fan:
- Galvanised sheet steel structure.
- Forward-curved impeller made of galvanised sheet steel.
- Approved in accordance with standard EN 12101-3. with certificate no.: 0370-CPR-0503
Motor:
- Class F motors with ball bearings and IP55 protection.
- Multi voltage motor. special design valid for 220/380V 60Hz. 254/440V 60Hz. 265/460V 60Hz. 277/480V 60Hz
- Maximum temperature of air to be carried: S1 continuous operation -20 ºC +120 ºC. S2 operation 300 ºC/2h and 400 ºC/2h.
Finish:
- Anticorrosive finished galvanised sheet steel.
On request:
- Extractor fans with 2-speed motors.
- Vertical outlet extractor fans.